Voltaglands waterproof cable glands, junction boxes and enclosure sealing parts

Technical Guide

Cable Gland Selection Guide: Thread, Cable OD and IP Rating

A practical reference for matching cable glands to your enclosure, cable and environment before you request a quotation.

1. Start with the thread standard

The mounting thread must match the enclosure hole or threaded entry. Three standards cover most industrial applications:

Standard Typical sizes Common use
Metric (M) M12 to M63 Modern EN 60423 equipment and most new control panels worldwide
PG PG7 to PG48 Legacy European cabinets and replacement work
NPT 1/4 in to 2 in North American conduit systems and tapered-thread entries

If the enclosure only has a plain hole, note the hole diameter and panel thickness instead of the thread.

2. Match the cable outside diameter to the sealing range

Every gland size clamps a defined cable OD range. A correct match keeps the IP rating; a loose or over-compressed seal does not.

How to measure

Measure the cable jacket diameter with calipers at the point where the gland will sit. If the cable is not round, use the largest dimension.

Choose the smallest suitable gland

When a cable OD fits two sizes, the smaller gland usually seals better and needs less panel space.

Clamping ranges differ between models and materials. Always confirm the exact sealing range on the product datasheet or in your quotation before ordering.

3. Choose the IP rating by exposure

Rating Protection Typical site
IP66 Dust-tight, resists powerful water jets Outdoor cabinets and washdown areas
IP67 Temporary immersion up to 1 m for 30 minutes Flood-risk pits and ground-level boxes
IP68 Continuous immersion at a stated depth Pumps, underwater or buried equipment

IP68 depth and duration are defined per model, so state the water depth in your inquiry.

4. Select the material for the environment

Material Strength Best for
PA66 nylon Light, economical, UV-resistant options General electrical boxes and solar combiner boxes
Nickel-plated brass High mechanical strength Machine building and vibration-prone equipment
Stainless steel 304/316 Corrosion resistance Marine, chemical and food-processing sites
EMC brass 360-degree shield contact Shielded cables in drives and instrumentation

5. What to send for a matched quotation

One complete set of parameters lets us reply with a matched component list:

  • Cable outside diameter for each line
  • Mounting thread or hole size and panel thickness
  • Material preference and IP rating target
  • Quantity per size, plus any reducers, plugs, locknuts and washers
  • Application environment: indoor, outdoor, washdown or corrosive

Ready to match your cable entry?

Send your parameters and receive a technically clear component list for review.

Request Quote

Email Sales WhatsApp Request Quote